Performance evaluation of data transmission in a single and double bus network within the utility substation based on IEC 61850
- Authors: Kumar, Shantanu , Das, Narottam , Muigai, John , Islam, Syed
- Date: 2014
- Type: Text , Conference proceedings , Conference paper
- Relation: 2014 IEEE Power and Energy Society General Meeting; National Harbor, United States; 27th-31st July 2014 Vol. 2014, p. 1-5
- Full Text: false
- Reviewed:
- Description: Communication between intelligent electronic devices (IED's) is an important feature of a utility substation automation system based on IEC 61850. Time critical information related to fault and overcurrent, under frequency messages for substation automation system (SAS) and the use of IED's from multiple vendors, has opened up issues related to a reliable protection system within the high voltage substation. Early detection of the delay in data transmission over a Generic Object Oriented Substation Event (GOOSE) network is an important step towards identification of problems associated with the dynamic protection system. It is observed that non critical messages adds up the queuing time and delays in the delivery of the messages which could be an issue in the reliable operation of a protection system. In this paper an Optimized Network Engineering Tool (OPNET) model is created, tested and analysed for a single and double bus configuration in detail for the delay encountered in data transfer within a typical zone substation. In order to understand the delay in transmission of packets, a 132/22kV zone substation model is analysed and results are discussed based on GOOSE communication in an IEC 61850 environment. Further, the delay in communication is compared and analysed between a single and double bus system of a 132/22kV substation to determine the best alternative technique available from protection point of view in a SAS network.
Performance evaluation of two interconnected high voltage utility substations using PRP topology based on IEC 62439-3
- Authors: Kumar, Shantanu , Das, Narottam , Islam, Syed
- Date: 2018
- Type: Text , Conference proceedings
- Relation: 2017 Australasian Universities Power Engineering Conference, AUPEC 2017; Melbourne, Australia; 19th-22nd November 2017 Vol. 2017, p. 1-5
- Full Text: false
- Reviewed:
- Description: In a modern power system network having multiple interconnected High Voltage (HV) substations, communication amongst Intelligent Electronic Devices (IED) becomes an important feature in an automation system. Time critical information, such as feeder faults, overcurrent, under frequency messages between multiple geographically isolated substations have opened up number of issues related to reliability in protection, automation and control. There are problems related to latency, data loss and transfer of Sampled Value (SV) packets transmitted to these inter-connected substations on radio wireless and Ethernet mode linked up in a Wide Area Network (WAN) configuration. Few other key area of concerns in a digital protection scheme are packet losses, errors in packet arrival at destination, latency in transmission, End to End delay in packet transfer due to flooding of the network, out of sequence packet arrival etc. Error prone packets could seriously compromise the protection scheme and endanger the safety of primary plant assets in a transmission substation. This paper investigates performance of SV packet transmission between two interconnected substations]. Practical simulations were performed to evaluate the performance of SV packets in a laboratory set up to assess the performance of digital protection scheme based on Parallel Redundancy Protocol (PRP) topology involving digital equipment such as Merger Units (MUs), switches, IEDs and Redundant boxes (Red box), etc.
Performance analysis of substation automation systems architecture based on IEC 61850
- Authors: Kumar, Shantanu , Das, Narottam , Islam, Syed
- Date: 2014
- Type: Text , Conference proceedings , Conference paper
- Relation: 24th Australasian Universities Power Engineering Conference, AUPEC 2014; Perth, Australia; 28th September-1st October 2014 p. 1-6
- Full Text: false
- Reviewed:
- Description: Digital Communications amongst multi-vendor intelligent electronic devices (IED's) is an important feature of a substation automation system (SAS). Measuring the propagation delays and assessing the interoperability performance of IED's in an Ethernet architecture play a critical role in the protection of important substation assets. Early detection of the loss of data packets in a star connected Ethernet architecture is an important step towards identification of delay in message transfer issue. This identification of the problem could lead to reliable operation of protection system and better understanding of the issues of interoperability which may improve the protection system from safety and availability point of view. This paper focuses on a star connected architecture using Optimized Network Engineering Tool (OPNET) software for a 132/22kV zone substation. It shares a practical case for measuring delay time in exchanging Generic Object Oriented Substation Event (GOOSE) messages amongst the IED's.
Analysis of IEC 61850 for a Reliable Communication System between Substations
- Authors: Yang, Xin , Das, Narottam , Islam, Syed
- Date: 2013
- Type: Text , Conference proceedings , Conference paper
- Relation: 2013 Australasian Universities Power Engineering Conference, AUPEC 2013; Hobart, Australia; 29th September-3rd October 2013 p. 1-6
- Full Text: false
- Reviewed:
- Description: IEC 61850 Standard was introduced to address the challenge presented by existence of the multiple protocols in substation communications, which include many proprietary protocols; and to address the challenge introduced by legacy complicated substation from both cost and complicity. In this paper, the simulation results of different types of IEC 61850 network system configurations using OPNET Modeler simulation software were presented and the influence on data rate and delay characteristics of these system configurations were evaluated. The simulated results confirm that the ring configured system suitable for higher loading characteristics and higher system reliability.