Impact of capacitive coupling circuit on online impulse frequency response of a power transformer
- Authors: Zhao, Zhongyong , Yao, Chenguo , Zhao, Xiaozhen , Hashemnia, Naser , Islam, Syed
- Date: 2016
- Type: Text , Journal article
- Relation: IEEE Transactions on Dielectrics and Electrical Insulation Vol. 23, no. 3 (2016), p. 1285-1293
- Full Text: false
- Reviewed:
- Description: Detecting the early signs of mechanical failures of power transformer winding is necessary and is possible with online monitoring techniques. Online impulse frequency response analysis (IFRA) is a promising diagnostic method when a transformer is in service. This paper examines the unrevealed problem existing in the method, namely, the impact of bushing capacitive coupling circuit on online impulse frequency response. An equivalent electrical model of capacitive coupling circuit and transformer winding is established. The frequency response of the capacitive coupling circuit is obtained to study its influence on online impulse frequency response. The parameter variations of capacitive coupling circuit caused by coupling capacitance variation and bushing dielectric breakdown are simulated to investigate their influence on online impulse frequency response signatures. A few experiments are eventually performed to verify the theoretical analysis and simulation results. This paper contributes to the application of online IFRA.
Understanding power transformer frequency response analysis signatures
- Authors: Abu-Siada, Ahmed , Hashemnia, Naser , Islam, Syed , Masoum, Mohammad
- Date: 2013
- Type: Text , Journal article
- Relation: IEEE Electrical Insulation Magazine Vol. 29, no. 3 (2013), p. 48-56
- Full Text: false
- Reviewed:
- Description: This paper presents a comprehensive analysis of the effects of various faults on the FRA signatures of a transformer simulated by a high-frequency model. The faults were simulated through changes in the values of some of the electrical components in the model. It was found that radial displacement of a winding alters the FRA signature over the entire frequency range (10 Hz-1 MHz), whereas changes due to axial displacement occur only at frequencies above 200 kHz. A Table listing various transformer faults and the associated changes in the FRA signature was compiled and could be used in the formulation of standard codes for power transformer FRA signature interpretation.