Performance evaluation of a process bus architecture in a zone substation based on IEC 61850-9-2
- Kumar, Shantanu, Das, Narottam, Islam, Syed
- Authors: Kumar, Shantanu , Das, Narottam , Islam, Syed
- Date: 2016
- Type: Text , Conference proceedings , Conference paper
- Relation: IEEE PES Asia-Pacific Power and Energy Engineering Conference, APPEEC 2015; Brisbane, Australia; 15th-18th November 2015 Vol. 2016, p. 1-5
- Full Text:
- Reviewed:
- Description: Ethernet communication has been the back bone of high speed communication in digital substations from protection relaying, control and automation perspective. Major substation manufacturers have been constantly upgrading softwares and adding new features in their Intelligent Electronic Devices (IED's) to carry out multiple functions in process bus devices. This paper presents simulation results with respect to the delay in packets transfer in an Ethernet environment. Understanding the delay in packet transfer of Generic Object Oriented Substation Event (GOOSE) and Sampled Values (SV) shall assist the user in understanding the substation automation, control and protection of substation primary plants such as current transformers (CT's), voltage transformers (VT's), circuit breakers etc. connected in the network during a fault condition Conventional substation uses Merging Units (MU's) to communicate with the IED's featuring IEC 61850-9-2 standard. This standard exhibits transparency and standardization of data communication while addressing issues related to reliability, packet sharing, and maintainability, etc. However, process bus architecture is yet to be widely accepted in the industry and needs further validation due to lack of confidence. This paper evaluates the performance of a digital protection scheme in a zone substation operating at 132kV, featuring IEC 61850-9-2 IED's and using an optimized network engineering tool (OPNET) simulator. Understanding the delay in receiving time critical GOOSE and sampled value SV messages from protection perspective is critical as loss of data could cause malfunction in the protection jeopardizing vital substation plants.
- Authors: Kumar, Shantanu , Das, Narottam , Islam, Syed
- Date: 2016
- Type: Text , Conference proceedings , Conference paper
- Relation: IEEE PES Asia-Pacific Power and Energy Engineering Conference, APPEEC 2015; Brisbane, Australia; 15th-18th November 2015 Vol. 2016, p. 1-5
- Full Text:
- Reviewed:
- Description: Ethernet communication has been the back bone of high speed communication in digital substations from protection relaying, control and automation perspective. Major substation manufacturers have been constantly upgrading softwares and adding new features in their Intelligent Electronic Devices (IED's) to carry out multiple functions in process bus devices. This paper presents simulation results with respect to the delay in packets transfer in an Ethernet environment. Understanding the delay in packet transfer of Generic Object Oriented Substation Event (GOOSE) and Sampled Values (SV) shall assist the user in understanding the substation automation, control and protection of substation primary plants such as current transformers (CT's), voltage transformers (VT's), circuit breakers etc. connected in the network during a fault condition Conventional substation uses Merging Units (MU's) to communicate with the IED's featuring IEC 61850-9-2 standard. This standard exhibits transparency and standardization of data communication while addressing issues related to reliability, packet sharing, and maintainability, etc. However, process bus architecture is yet to be widely accepted in the industry and needs further validation due to lack of confidence. This paper evaluates the performance of a digital protection scheme in a zone substation operating at 132kV, featuring IEC 61850-9-2 IED's and using an optimized network engineering tool (OPNET) simulator. Understanding the delay in receiving time critical GOOSE and sampled value SV messages from protection perspective is critical as loss of data could cause malfunction in the protection jeopardizing vital substation plants.
Performance monitoring of a PMU in a microgrid environment based on IEC 61850-90-5
- Kumar, Shantanu, Das, Narottam, Islam, Syed
- Authors: Kumar, Shantanu , Das, Narottam , Islam, Syed
- Date: 2016
- Type: Text , Conference proceedings , Conference paper
- Relation: 2016 Australasian Universities Power Engineering Conference, AUPEC 2016; Brisbane, Australia; 25th-28th September 2016 p. 1-5
- Full Text:
- Reviewed:
- Description: Reliable protection, communication and control are the key features of a digital protection scheme in a utility substation. Microgrid is an alternative solution of installing long Transmission & Distribution lines could be cost prohibitive. There are number of Intelligent Electronic Devices (IEDs) which could find applications in controlling and monitoring of power network in a Microgrid set up and one such device is Phasor Measurement Unit (PMU). It is a microprocessor based intelligent device which gathers high-resolution data, checks the power quality and records disturbances. However, few issues that remains to be addressed such as, interoperability in a multi-vendor equipment and coordination between individual control systems in an integrated scheme. In this paper, an Operational Network Technology (OPNET) software model of a PMU has been designed and tested for its performance in a Microgrid environment based on IEC 61850-90-5 standard.
- Authors: Kumar, Shantanu , Das, Narottam , Islam, Syed
- Date: 2016
- Type: Text , Conference proceedings , Conference paper
- Relation: 2016 Australasian Universities Power Engineering Conference, AUPEC 2016; Brisbane, Australia; 25th-28th September 2016 p. 1-5
- Full Text:
- Reviewed:
- Description: Reliable protection, communication and control are the key features of a digital protection scheme in a utility substation. Microgrid is an alternative solution of installing long Transmission & Distribution lines could be cost prohibitive. There are number of Intelligent Electronic Devices (IEDs) which could find applications in controlling and monitoring of power network in a Microgrid set up and one such device is Phasor Measurement Unit (PMU). It is a microprocessor based intelligent device which gathers high-resolution data, checks the power quality and records disturbances. However, few issues that remains to be addressed such as, interoperability in a multi-vendor equipment and coordination between individual control systems in an integrated scheme. In this paper, an Operational Network Technology (OPNET) software model of a PMU has been designed and tested for its performance in a Microgrid environment based on IEC 61850-90-5 standard.
Software implementation of two seamless redundant topologies in a digital protection system based on IEC 62439-3
- Kumar, Shantanu, Das, Narottam, Islam, Syed
- Authors: Kumar, Shantanu , Das, Narottam , Islam, Syed
- Date: 2016
- Type: Text , Conference proceedings , Conference paper
- Relation: 2016 Australasian Universities Power Engineering Conference, AUPEC 2016; Brisbane, Australia; 25th-28th September 2016 p. 1-5
- Full Text:
- Reviewed:
- Description: Substations are the junctions of any transmission and distribution network in utilities. They carry bulk power to the customers using transmission network involving high voltage (HV) apparatus. Protection of HV equipment during a fault is the primary concern of an operator. Advancement in design and manufacturing of Intelligent Electronic Devices (IEDs) and IEC 61850 are finding increased application in utilities from automation and communication perspective, which addresses few shortcomings that couldn't be resolved in a conventional system. However there are few challenges in the digital scheme such as end to end delays in the packet transfer and interoperability of devices. Utilities are able to perceive these benefits by leveraging on IEC 62439-3 which has two important topologies i.e. Parallel Redundancy Protocol (PRP) and High-availability Seamless Redundancy (HSR). It offers seamless redundancy in digital protection network without compromising the availability and downtime cost. In this paper, an Optimized Network Engineering Tool (OPNET) is used to simulate and compare the performance of these topologies with respect to delay time.
- Description: Proceedings of the 2016 Australasian Universities Power Engineering Conference, AUPEC 2016
- Authors: Kumar, Shantanu , Das, Narottam , Islam, Syed
- Date: 2016
- Type: Text , Conference proceedings , Conference paper
- Relation: 2016 Australasian Universities Power Engineering Conference, AUPEC 2016; Brisbane, Australia; 25th-28th September 2016 p. 1-5
- Full Text:
- Reviewed:
- Description: Substations are the junctions of any transmission and distribution network in utilities. They carry bulk power to the customers using transmission network involving high voltage (HV) apparatus. Protection of HV equipment during a fault is the primary concern of an operator. Advancement in design and manufacturing of Intelligent Electronic Devices (IEDs) and IEC 61850 are finding increased application in utilities from automation and communication perspective, which addresses few shortcomings that couldn't be resolved in a conventional system. However there are few challenges in the digital scheme such as end to end delays in the packet transfer and interoperability of devices. Utilities are able to perceive these benefits by leveraging on IEC 62439-3 which has two important topologies i.e. Parallel Redundancy Protocol (PRP) and High-availability Seamless Redundancy (HSR). It offers seamless redundancy in digital protection network without compromising the availability and downtime cost. In this paper, an Optimized Network Engineering Tool (OPNET) is used to simulate and compare the performance of these topologies with respect to delay time.
- Description: Proceedings of the 2016 Australasian Universities Power Engineering Conference, AUPEC 2016
Analysis of end-to-end delay characteristics for various packets in IEC 61850 substation communications system
- Das, Narottam, Ma, Wu, Islam, Syed
- Authors: Das, Narottam , Ma, Wu , Islam, Syed
- Date: 2015
- Type: Text , Conference proceedings , Conference paper
- Relation: 25th Australasian Universities Power Engineering Conference, AUPEC 2015, Wollongong, Australia; 27th-30th September 2015 p. 1-5
- Full Text:
- Reviewed:
- Description: Substation plays an important role in power system communications for safe and reliable operation of entire power networks. Substation communication networks are connected with various substation intelligent electronic devices (IEDs), which is substation systems lifeblood and the system availability is decided by its real-Time performance. International Electro-Technical Commission (IEC) has been developed the standards based on object-oriented technologies for substation automation. IEC 61850 protocol has been applied widely in substation communication applications. It presents new challenges to realtime performance simulation and testing of protective relays. In this paper, an optimized network engineering tool (OPNET) or Riverbed modeler simulation tool/ software has been used for the modeling of IED in substation level network. Based on the simulation results, different types of data stream have been discussed, such as, periodic data stream, random data stream and burst data steam. The typical studies using these models, to construct substation automation system (SAS) network on the OPNET modeler or Riverbed modeler was made to reveal the impact of each affecting parameter or factor to the real-Time performance of substation communications system, which is also incorporated in this report.
- Description: 2015 Australasian Universities Power Engineering Conference: Challenges for Future Grids, AUPEC 2015
- Authors: Das, Narottam , Ma, Wu , Islam, Syed
- Date: 2015
- Type: Text , Conference proceedings , Conference paper
- Relation: 25th Australasian Universities Power Engineering Conference, AUPEC 2015, Wollongong, Australia; 27th-30th September 2015 p. 1-5
- Full Text:
- Reviewed:
- Description: Substation plays an important role in power system communications for safe and reliable operation of entire power networks. Substation communication networks are connected with various substation intelligent electronic devices (IEDs), which is substation systems lifeblood and the system availability is decided by its real-Time performance. International Electro-Technical Commission (IEC) has been developed the standards based on object-oriented technologies for substation automation. IEC 61850 protocol has been applied widely in substation communication applications. It presents new challenges to realtime performance simulation and testing of protective relays. In this paper, an optimized network engineering tool (OPNET) or Riverbed modeler simulation tool/ software has been used for the modeling of IED in substation level network. Based on the simulation results, different types of data stream have been discussed, such as, periodic data stream, random data stream and burst data steam. The typical studies using these models, to construct substation automation system (SAS) network on the OPNET modeler or Riverbed modeler was made to reveal the impact of each affecting parameter or factor to the real-Time performance of substation communications system, which is also incorporated in this report.
- Description: 2015 Australasian Universities Power Engineering Conference: Challenges for Future Grids, AUPEC 2015
High performance communication redundancy in a digital substation based on IEC 62439-3 with a station bus configuration
- Kumar, Shantanu, Das, Narottam, Islam, Syed
- Authors: Kumar, Shantanu , Das, Narottam , Islam, Syed
- Date: 2015
- Type: Text , Conference proceedings , Conference paper
- Relation: 25th Australasian Universities Power Engineering Conference, AUPEC 2015; Wollongong, Australia; 27th-30th September 2015 p. 1-5
- Full Text:
- Reviewed:
- Description: High speed communication is critical in a digital substation from protection, control and automation perspectives. Although International Electro-Technical Commission (IEC) 61850 standard has proven to be a reliable guide for the substation automation and communication systems, yet it has few shortcomings in offering redundancies in the protection architecture, which has been addressed better in IEC 62439-3 standard encompassing Parallel Redundancy Protocol (PRP) and High-Availability Seamless Redundancy (HSR). Due to single port failure, data losses and interoperability issues related to multi-vendor equipment, IEC working committee had to look beyond IEC 61850 standard. The enhanced features in a Doubly Attached Node components based on IEC 62439-3 provides redundancy in protection having two active frames circulating data packets in the ring. These frames send out copies in the ring and should one of the frame is lost, the other copy manages to reach the destination node via an alternate path, ensuring flawless data transfer at a significant faster speed using multi-vendor equipment and fault resilient circuits. The PRP and HSR topologies provides higher performance in a digitally protected substation and promise better future over the IEC 61850 standard due to its faster processing capabilities, increased availability and minimum delay in data packet transfer and wireless communication in the network. This paper exhibits the performance of PRP and HSR topologies focusing on the redundancy achievement within the network and at the end nodes of a station bus ring architecture, based on IEC 62439-3.
- Authors: Kumar, Shantanu , Das, Narottam , Islam, Syed
- Date: 2015
- Type: Text , Conference proceedings , Conference paper
- Relation: 25th Australasian Universities Power Engineering Conference, AUPEC 2015; Wollongong, Australia; 27th-30th September 2015 p. 1-5
- Full Text:
- Reviewed:
- Description: High speed communication is critical in a digital substation from protection, control and automation perspectives. Although International Electro-Technical Commission (IEC) 61850 standard has proven to be a reliable guide for the substation automation and communication systems, yet it has few shortcomings in offering redundancies in the protection architecture, which has been addressed better in IEC 62439-3 standard encompassing Parallel Redundancy Protocol (PRP) and High-Availability Seamless Redundancy (HSR). Due to single port failure, data losses and interoperability issues related to multi-vendor equipment, IEC working committee had to look beyond IEC 61850 standard. The enhanced features in a Doubly Attached Node components based on IEC 62439-3 provides redundancy in protection having two active frames circulating data packets in the ring. These frames send out copies in the ring and should one of the frame is lost, the other copy manages to reach the destination node via an alternate path, ensuring flawless data transfer at a significant faster speed using multi-vendor equipment and fault resilient circuits. The PRP and HSR topologies provides higher performance in a digitally protected substation and promise better future over the IEC 61850 standard due to its faster processing capabilities, increased availability and minimum delay in data packet transfer and wireless communication in the network. This paper exhibits the performance of PRP and HSR topologies focusing on the redundancy achievement within the network and at the end nodes of a station bus ring architecture, based on IEC 62439-3.
- «
- ‹